Home › Cables & fuses

AC voltage drop calculator

Long mains leads lose voltage, especially at high current. Check your hook-up cable, extension reel or shed supply. Always have mains installations designed and checked by a qualified electrician.

A
V
230 V UK/EU, 120 V US.

Results

Voltage drop—
Percentage—
Voltage at the end—
Heat in the cable—

The formula

Voltage drop = 2 × Length × Current × 0.01724 ÷ Area (mm²)

This resistive calculation is accurate for the small cable sizes used in leads and sub-mains. For large cables and long distances, an electrician will also consider reactance and the drop already present at the supply.

Worked example

A standard 25 m 2.5 mm² campsite hook-up lead at 16 A: 2 × 25 × 16 × 0.01724 ÷ 2.5 = 5.5 V, or 2.4% at 230 V. That's fine. A 50 m reel of 1.5 mm² cable at 13 A would lose 15 V (6.5%), and must be fully unwound to avoid overheating.

Guidance

Frequently asked questions

What is the maximum length for a hook-up cable?

UK guidance limits caravan hook-up leads to 25 m in one length, with 2.5 mm² conductors for 16 A.

How much voltage do I lose on a 50m extension lead?

With 1.5 mm² cable at 10 A, about 11.5 V (5% at 230 V). At 13 A, about 15 V.