DC cable size calculator

Enter the current and the one-way cable length, choose how much voltage drop you'll accept, and get the smallest standard cable that meets both voltage drop and current rating.

A
Use the maximum continuous current, or the fuse rating for the safest result.
V

Results

Recommended cable—
Limited by—
Actual voltage drop—
Minimum area for voltage drop—
Guide current rating—

How the cable size is chosen

Minimum area (mm²) = 2 × Length × Current × 0.01724 ÷ (Voltage × Max drop %)

The calculator then picks the smallest standard size that is both above this area and has a guide current rating above your current. On short, high-current runs (like inverter cables) the current rating usually decides; on long, low-current runs (like lighting or solar cable) voltage drop decides.

Worked example

A 30 A DC-DC charger, 3 m from the starter battery, 3% maximum drop at 12 V: 2 × 3 × 30 × 0.01724 ÷ 0.36 = 8.6 mm², so 10 mm² (or 6 AWG).

Common sizes at 12 V, 3% drop (standard PVC cable)

Current1 m (3 ft)3 m (10 ft)5 m (16 ft)
10 A1 mm²4 mm²6 mm²
20 A4 mm²6 mm²10 mm²
50 A16 mm²16 mm²25 mm²
100 A35 mm²35 mm²50 mm²
200 A120 mm²120 mm²120 mm²

On short, high-current runs the conservative PVC current rating decides the size. With 105 °C cable run on its own, those sizes can usually drop by one or two steps; choose that cable type above to see.

Current ratings are guide figures for single-core copper cable. 'Standard PVC' uses conservative values for 70 °C insulation, bundled or enclosed; '105 °C' uses typical marine-table values for high-temperature cable run on its own. Always check the cable maker's rating, and derate for hot spaces such as engine bays.

Good practice

Frequently asked questions

What size cable for a 2000W inverter at 12V?

It draws about 190 A at full load. On a short run (1–1.5 m) with 105 °C cable, about 35–50 mm² (2 to 1/0 AWG); with standard PVC cable, considerably larger. The inverter manual usually states a minimum, so use whichever is bigger.

What size cable from solar panel to controller?

Solar current is low, so voltage drop decides. A 10 A string over 10 m at 40 V needs about 2.5–4 mm² for under 3% drop; 4 mm² and 6 mm² solar cable are standard.

Is mm² the same as AWG?

No. AWG numbers get smaller as cable gets thicker. 10 mm² is close to 8 AWG (8.4 mm²) and 6 AWG (13.3 mm²) sits between 10 and 16 mm². Use the AWG to mm² converter.