Connecting a generator to your house: transfer switches and interlocks
Why double-ended leads and back-feeding are so dangerous, the safe options from extension leads to automatic transfer switches, the rules in the UK, US and Australia, earthing and the neutral, sizing circuits, and using it safely.
By Michael Johnson · Updated 17 November 2026 · How we check our guides
Plugging a generator into a house the wrong way is one of the most dangerous mistakes people make in a power cut. A "suicide lead" (a cable with a plug on both ends) can electrocute you, and power fed back into the grid can kill line workers repairing it. This guide explains the safe ways to run a home from a generator or battery: changeover switches, interlock kits, inlet sockets and automatic transfer switches, and what the rules say in the UK, USA and Australia.
1. Why you need a transfer switch
- Back-feeding: without a switch that disconnects the grid, generator power flows out through your meter into the street. The transformer steps it up to thousands of volts, which can kill line workers who think the line is dead.
- Damage: when grid power returns, it meets the generator's output out of phase, which can wreck the generator and start a fire.
- Shock: a suicide lead leaves exposed live pins.
- A changeover or transfer switch makes it physically impossible to connect the grid and the generator at the same time.
2. The safe options
| Option | How it works | Pros | Cons |
|---|---|---|---|
| Extension leads to appliances | Run appliances directly from the generator's sockets | Cheap; no wiring work | Can't run hard-wired loads like boilers and well pumps; leads through windows |
| Manual changeover switch with inlet socket | A 3-position switch (mains / off / generator) at the consumer unit, and an outdoor inlet for the generator lead | Runs chosen circuits or the whole house safely | Electrician install; switch over by hand |
| Interlock kit (US) | A sliding plate that stops the main breaker and generator breaker being on together | Lower cost than a transfer switch; whole panel available | Must be listed for your panel; you manage loads by hand |
| Manual transfer switch sub-panel (US) | Selected circuits wired through a small transfer panel | Simple to use; limits loads to what the generator can run | Only selected circuits |
| Automatic transfer switch (ATS) | Detects the outage, starts a standby generator and switches over | Hands-free; seconds of interruption | Expensive; needs a standby (auto-start) generator |
3. UK rules
- BS 7671 (the IET Wiring Regulations) requires that a generator used as a standby supply can't operate in parallel with the public supply unless it's designed and approved for that. In practice, a changeover switch that breaks all live conductors, including neutral.
- The work is notifiable under Part P in England and Wales when it adds a new circuit or alters the consumer unit; use a registered electrician who will certify it.
- Tell your distribution network operator (DNO) about a permanently installed standby generator.
- Generators designed to export (in parallel with the grid) come under separate connection rules (Engineering Recommendations G98/G99) and need the DNO's approval.
- Report power cuts by calling 105.
4. US rules
- The National Electrical Code requires a transfer switch or listed interlock for any generator connected to a building's wiring (Article 702 for optional standby systems).
- Most areas need an electrical permit and inspection.
- Use a power inlet box rated for the generator, and a cord with the right locking connectors (for example L14-30 for 30 A at 120/240 V).
- The CPSC and utilities warn that back-feeding is illegal in many states and kills line workers every year.
5. Australian rules
- Under AS/NZS 3000 and AS/NZS 3010, connecting a generator to a home's wiring must be done by a licensed electrician, with a changeover switch that isolates the grid.
- Plugging a generator into a power point (using a double-ended lead) is illegal and dangerous.
- State regulators (for example Energy Safe Victoria, Electrical Safety Office Queensland, Building and Energy WA) publish generator safety guidance; follow it after storms and bushfires.
6. Earthing and the neutral
- When the house is switched to the generator, the generator becomes the source and the installation's earth arrangement changes. Whether the neutral is switched and where the neutral–earth bond sits must match the generator and the system type.
- In the UK, changeover switches for standby generators normally switch the neutral as well as the line conductors.
- Many portable generators have a floating neutral; an electrician may need to add a bond or use a generator with a bonded neutral so RCDs work.
- See the off-grid earthing guide.
7. Sizing the generator and circuits
- Decide which circuits matter: heating controls and boiler, fridge and freezer, lights, sockets for chargers, and well or sump pumps.
- Add up the running watts and the biggest start-up surge, then add 25% margin. Use the generator size calculator.
- Gas boilers and some heat pumps need clean, stable power: use an inverter generator. See the keeping warm in a power cut guide.
- Electric showers, ovens and immersion heaters usually need to stay off.
8. Home batteries and inverters
- Home batteries with backup (EPS) have a built-in automatic switch that isolates from the grid. They only back up the circuits wired to them.
- Inverters and power stations must not be plugged into house sockets either; the same back-feeding rules apply.
- Some systems accept a generator input to recharge the battery during long cuts. See the home backup power guide and the EV home backup guide.
9. Using it safely in a power cut
- Put the generator outdoors, away from doors, windows and vents, on a level surface. Fit a carbon monoxide alarm indoors.
- Turn the changeover switch to "off", then connect the generator lead to the inlet.
- Start the generator and let it settle.
- Switch over to "generator" and turn on circuits one at a time, biggest first.
- When power returns: switch over to "mains", then stop the generator.
- Refuel only when cool. See the fuel storage calculator.
10. Frequently asked questions
Can I plug my generator into a wall socket?
No. A double-ended lead leaves live pins exposed and can back-feed the grid, which can kill line workers. Use extension leads to appliances, or have a changeover switch and inlet fitted.
Do I need an electrician to install a generator changeover switch?
Yes. In the UK it's notifiable work under the Wiring Regulations, in the US it usually needs a permit and inspection, and in Australia it must be done by a licensed electrician.
What is a generator interlock kit?
A plate fitted to a US breaker panel that stops the main breaker and generator breaker being on at the same time. It's a cheaper alternative to a transfer switch when listed for your panel.
What size generator do I need to run my house?
Essentials (boiler, fridge, freezer, lights, chargers) usually need 2–4 kW. Add up the running watts, allow for start-up surges and add 25%.
11. Sources
- IET, operation of portable generators (guidance): electrical.theiet.org
- Oregon Building Codes Division, generator connection: oregon.gov
- Energy Safe Victoria, generator safety fact sheet (2026): energysafe.vic.gov.au
- Electrical Safety Office Queensland, permanently connected generators: electricalsafety.qld.gov.au
- Building and Energy WA, safe use of portable generators: commerce.wa.gov.au