How to run a capacity test
- Charge the battery to 100% and let it finish absorption (and balancing, for lithium).
- Rest it for an hour.
- Discharge at a steady load, ideally about 0.05C for lead-acid (5 A for a 100 Ah battery, its 20-hour rate) or 0.1–0.2C for lithium.
- Stop at the cut-off: about 10.5 V for 12 V lead-acid, or when the lithium BMS or 10–11 V cut-off stops it.
- Record the amp-hours with a shunt monitor, or the time and current.
How it's worked out
- Lead-acid batteries are rated at the 20-hour rate and deliver less at higher currents (Peukert exponent 1.1–1.3). Lithium barely changes (about 1.05).
- Cold reduces capacity: about 0.8% per °C below 25 °C for lead-acid, and about 0.3% for lithium.
See the battery monitoring guide, the Peukert calculator and the guide to buying used batteries.
Frequently asked questions
How do I test a battery's real capacity?
Charge it fully, then discharge it at a steady, known current until the low-voltage cut-off, and multiply current by hours (or read the amp-hours from a shunt monitor).
What is a good battery state of health?
Above 90% is healthy, 80–90% shows normal wear, 60–80% is worn, and below 60% usually means replacement.
Why does my lead-acid battery give less than its rated Ah?
Ratings are at the 20-hour rate. Discharging faster, or in the cold, gives less (the Peukert effect).