How it's worked out
- Modern inverter-driven heat pumps ramp up gently, so they don't have the big start-up surge of older fixed-speed units. Older or fixed-speed units can need two to three times running current to start.
- Cold weather lowers the COP, so the heat pump draws more electricity just when power cuts are most likely.
- Some generators struggle with the sudden load changes when a heat pump cycles off. An inverter generator with good voltage regulation, or running through a battery inverter, is kinder to the electronics.
Typical results (70% load, COP 2.5, 150 W pumps, 300 W other loads, 10 kWh battery)
| Heat pump | Average draw | Battery run time | Inverter needed |
|---|---|---|---|
| 5 kW | About 1.55 kW | About 4.9 hours | About 3.1 kW |
| 7 kW | About 2.11 kW | About 3.7 hours | About 4.1 kW |
| 10 kW | About 2.95 kW | About 2.8 hours | About 5.6 kW |
For frost protection, which circuits to back up and generator connection, see the heat pumps in a power cut guide.
Frequently asked questions
Can a home battery run a heat pump in a power cut?
Yes, if the battery has a backup output large enough (often 3–6 kW) and the heat pump is on the backed-up circuit. A 10 kWh battery typically runs a 7 kW heat pump for 3–5 hours in cold weather.
What size generator do I need for a heat pump?
For a typical 5–10 kW air source heat pump, about 3–7 kW, connected through a proper changeover switch. An inverter generator gives cleaner power.
What happens to a heat pump in a power cut?
It stops. It usually restarts by itself when power returns, but outdoor pipework can freeze in a long winter cut unless it has glycol or antifreeze valves.