Heat pumps in a power cut: backup power and frost protection
What happens in a power cut, how long the house stays warm, frost protection, how much power a heat pump needs, running it from a home battery or generator, hybrid systems, restarting, and a power cut plan.
By Michael Johnson · Updated 18 November 2026 · How we check our guides
A gas boiler stops in a power cut too, but a heat pump draws far more electricity, so it's much harder to keep going on backup. And if the power is off for a long time in freezing weather, an air source heat pump's outdoor pipework can freeze. With hundreds of thousands of UK homes now heated by heat pumps, this guide explains what happens in a power cut, how long the house stays warm, frost protection, running a heat pump from a home battery or generator, and a practical plan for keeping warm.
1. What happens in a power cut
- The heat pump, its circulation pump and controls stop. Heating and hot water pause.
- Heat pumps don't export electricity, so they don't need to disconnect like solar or batteries; they simply stop.
- Most restart automatically when power returns, though some take a while to warm up again or need a setting chosen.
- A hot water cylinder stays hot for a day or more if it's well insulated.
- Underfloor heating and well-insulated homes cool slowly; radiator systems in draughty homes cool faster.
2. How long the house stays warm
| Home | Time to fall from 20 °C to about 15 °C at 0 °C outside |
|---|---|
| Well-insulated new build or retrofitted home | About a day or more |
| Typical 1970s–2000s home with cavity and loft insulation | About 6–12 hours |
| Older, draughty or solid-wall home | A few hours |
Heat pump homes are usually better insulated, which helps. Check yours with the house cool-down calculator.
3. Frost protection: the real risk
When the power is on, heat pumps protect themselves: if the water gets cold, the circulation pump and compressor run to keep it above freezing. In a power cut, that protection stops.
- Monobloc heat pumps (the most common type in the UK) have water in the outdoor unit and the pipes running to it, which can freeze in a long cut in sub-zero weather.
- Split systems carry refrigerant to the outdoor unit and keep water indoors, so they're less exposed.
- Glycol (antifreeze) in the system lowers the freezing point to around −15 °C, at the cost of some efficiency and more pumping.
- Antifreeze valves on the outdoor flow and return open below about 3 °C and drain water from the exposed pipes before it can freeze, then close above about 4 °C. The system then needs refilling and repressurising, which may need an installer.
- One installer reported only two freezing failures in over 10,000 units, both after very long outages or misuse. The risk is real but rare.
- Ask your installer which protection your system has. If the answer is "the heat pump protects itself", that only works with power.
In a long winter power cut, keeping the heat pump's circulation pump and controls powered (a few hundred watts) protects against freezing even if you can't run the compressor.
4. How much power a heat pump needs
| Heat pump | Full output draw at COP 2.5 | Typical draw on a cold day (70% load) |
|---|---|---|
| 5 kW | About 2.2 kW | About 1.6 kW |
| 7 kW | About 3 kW | About 2.1 kW |
| 10 kW | About 4.2 kW | About 3 kW |
| Pumps and controls only (frost protection) | About 100–200 W | |
- Inverter-driven heat pumps ramp up gently with little start-up surge. Older fixed-speed units can draw two to three times running current for a moment when they start.
- COP falls as the weather gets colder, so the draw rises when you need it most.
- Some heat pumps let the installer cap maximum power, which helps on a limited backup supply.
5. Running it from a home battery
- Most home batteries don't back up the house by default. Many have a backup port (EPS) feeding a few chosen circuits; whole-home backup needs a backup gateway or changeover.
- Check the backup output rating: many are 3–5 kW, which may run a 5–7 kW heat pump at reduced output but not a large one at full power.
- A 10 kWh battery typically runs a 7 kW heat pump for 3–5 hours on a cold day; frost protection alone (pumps and controls) could run for days.
- With a backup gateway, solar can keep charging the battery during a daytime power cut.
- Ask your installer whether the heat pump is on the backed-up circuit, and whether you can switch it to "frost protection only" to stretch the battery.
- See the home backup power guide and the home backup battery calculator.
6. Running it from a generator
- A generator must be connected through a proper changeover switch fitted by an electrician, never backfed through a socket. See the connecting a generator safely guide.
- Size it above the heat pump's full-output draw plus other essentials: typically 3–7 kW for a domestic heat pump. Use the generator size calculator.
- Heat pump electronics can be sensitive to voltage and frequency swings. One UK owner found a large generator's voltage spiked above 270 V each time the heat pump stopped, tripping its protection. An inverter generator, or running through a battery inverter, gives cleaner power.
- Run generators outside, away from doors and windows, with a CO alarm indoors.
- Fuel use matters: a 5 kW generator at half load might burn around 1–1.5 litres an hour. See the generator fuel calculator.
7. Hybrid systems and back-up heat
- A hybrid system (heat pump plus gas or oil boiler) still needs electricity for the boiler's controls and pump, but only about 100–200 W, so a small battery or power station can keep it running.
- A wood burner is the most reliable back-up heat in a power cut. See the wood burner guide.
- Heated throws and electric blankets on a power station use a few tens of watts. See keeping warm in a power cut.
- Never use gas ovens, barbecues or patio heaters indoors.
8. When the power comes back
- Most heat pumps restart on their own after a short delay. If yours doesn't, check the controller for error codes and follow the manual.
- After a long cut, the system may need to reheat a cold house slowly: expect high power use for a while.
- If antifreeze valves have opened, check the system pressure and call the installer to refill.
- If the outdoor unit is iced up and the fan can't move air, switch it off and let it thaw, or call the installer.
- Check the hot water cylinder reaches 60 °C again for legionella control.
9. A power cut plan for heat pump homes
- Find out from your installer: frost protection type, whether it auto-restarts, and its maximum power draw.
- If you have a battery, confirm what's on the backup circuit and whether it covers the heat pump's pumps and controls.
- Have a non-electric heat source or warm layers, blankets and hot water bottles ready.
- Know where the heat pump's isolator is.
- Join the Priority Services Register if anyone at home is vulnerable to cold.
- Read the power cut plan and winter blackouts guide.
10. Frequently asked questions
Do heat pumps work in a power cut?
No. They need electricity to run the compressor, fan and pumps. They usually restart automatically when power returns.
Can a heat pump freeze in a power cut?
A monobloc's outdoor pipes can freeze in a long cut in sub-zero weather if the system has no glycol or antifreeze valves. It's rare, but worth checking with your installer.
Can I run my heat pump on a generator?
Yes, through an electrician-fitted changeover switch, with a generator sized above the heat pump's full draw. An inverter generator gives cleaner power for the electronics.
How long will a home battery run a heat pump?
Typically 3–5 hours for a 7 kW heat pump on a cold day from a 10 kWh battery, if the battery's backup output is big enough. Running only the pumps for frost protection lasts much longer.
11. Sources
- UK Power Networks, power cuts, voltage issues and your low carbon technologies: ukpowernetworks.co.uk
- Renewable Heating Hub, heat pump freeze protection: are we overreacting?: renewableheatinghub.co.uk
- Altecnic, anti-freeze valves FAQs: altecnic.co.uk
- Heatable, will a home battery keep your lights on in a power cut?: heatable.co.uk
- OVO Energy forum, heat pump running from an electric generator: forum.ovoenergy.com
- WMCA, heat pump turns off: wmca.org.uk