DC cable sizing
The two checks, voltage drop and the formula, worked examples, acceptable drop, current rating, typical sizes, metric and AWG sizes, cable types, and fusing the cable.
By Michael Johnson · Updated 19 November 2026 · How we check our guides
Undersized cable is the most common fault in DIY 12 V and 24 V systems. At low voltage, a few tenths of a volt lost in the cable is a large share of the supply, so inverters cut out, fridges stall and chargers never finish. Worse, a cable that's too thin for its fuse can overheat before the fuse blows. This guide explains the two separate checks every DC cable needs (current rating and voltage drop), the voltage drop formula with worked examples, typical sizes for common jobs, metric and AWG sizes, cable types, and how the fuse ties it all together.
1. The two checks
- Current rating (ampacity): how much current the cable can carry without overheating. It depends on the cross-section, the insulation's temperature rating and how the cable is installed (in free air, bundled, in conduit or in insulation).
- Voltage drop: how many volts are lost along the cable's length. Long low-voltage runs are almost always limited by voltage drop, not by heat.
- Work out both, and use whichever gives the larger cable.
2. Voltage drop and the formula
For a DC circuit, the current flows out and back, so the cable length counts twice:
Voltage drop (V) = 2 × length one way (m) × current (A) × 0.0172 ÷ cross-section (mm²)
Rearranged to find the size you need:
Cross-section (mm²) = 2 × length (m) × current (A) × 0.0172 ÷ allowed drop (V)
- 0.0172 is the resistivity of copper in ohm·mm² per metre at 20 °C. Warm cable has slightly higher resistance, so round up to the next standard size.
- The allowed drop in volts is the system voltage × the percentage you accept (for example 12 V × 3% = 0.36 V).
- Use the DC cable size calculator and the voltage drop calculator to do the arithmetic.
3. Worked examples
| Circuit | Working | Result |
|---|---|---|
| 12 V, 20 A, 5 m one way, 3% drop | 2 × 5 × 20 × 0.0172 ÷ 0.36 = 9.6 mm² | Use 10 mm² |
| Same load at 24 V (10 A), 3% drop | 2 × 5 × 10 × 0.0172 ÷ 0.72 = 2.4 mm² | Use 2.5 mm² (check the current rating) |
| 12 V fridge, 6 A, 4 m, 3% drop | 2 × 4 × 6 × 0.0172 ÷ 0.36 = 2.3 mm² | Use 2.5 mm² (4 mm² if the fridge is fussy about voltage) |
| 12 V, 1,000 W inverter (about 100 A), 1.5 m, 2% drop | 2 × 1.5 × 100 × 0.0172 ÷ 0.24 = 21.5 mm² | 25 mm² for drop; check the inverter manual, which often asks for 35 mm² for current and surge |
Doubling the system voltage halves the current for the same power, and cuts the cable size needed for the same percentage drop to a quarter. That's why larger systems move to 24 V or 48 V. See the 12 V, 24 V or 48 V guide.
4. How much drop is acceptable
| Circuit | Typical target |
|---|---|
| Battery to inverter, battery to charger | 1–2% |
| Solar panels to charge controller | 1–3% |
| Compressor fridges and pumps | 2–3% (low voltage causes cut-outs) |
| Lighting and small loads | 3–5% |
5. Current rating and installation
- Current ratings come from the cable maker's tables or wiring standards, and fall when cables are bundled, enclosed, run through insulation or in hot engine bays.
- Higher-temperature insulation (for example 105 °C or 110 °C rated cable) carries more current than 70 °C PVC of the same size, but the terminals must also cope.
- Short, high-current battery and inverter cables are usually limited by heat and surge; long low-current runs by voltage drop.
- Never use the smallest size from a "maximum current" chart for a long run.
6. Typical sizes for common jobs
These are starting points for short runs; always check with the formula and the equipment manual.
| Job | Often used |
|---|---|
| LED lights, USB sockets | 1.5 mm² |
| 12 V fridge, water pump | 2.5–4 mm² |
| Solar panel strings (PV cable) | 4 or 6 mm² |
| DC-DC charger (20–30 A) | 10–16 mm² |
| 1,000 W inverter at 12 V | 25–35 mm² |
| 2,000–3,000 W inverter at 12 V | 50–95 mm² (better to use 24 V or 48 V) |
7. Metric and AWG sizes
American cable is sized in AWG, where a smaller number means a thicker cable. Approximate equivalents:
| Metric | Nearest AWG |
|---|---|
| 1.5 mm² | 16 AWG (1.3 mm²) |
| 2.5 mm² | 14 AWG (2.1 mm²) or 13 AWG |
| 4 mm² | 12 AWG (3.3 mm²) |
| 6 mm² | 10 AWG (5.3 mm²) |
| 10 mm² | 8 AWG (8.4 mm²) |
| 16 mm² | 6 AWG (13.3 mm²) |
| 25 mm² | 4 AWG (21.2 mm²) |
| 35 mm² | 2 AWG (33.6 mm²) |
| 50 mm² | 1/0 AWG (53.5 mm²) |
| 70 mm² | 2/0 AWG (67.4 mm²) |
When converting, round up to the larger cable. Some cheap cable labelled with an AWG size has less copper than it should (often called copper-clad aluminium or undersized strands); buy from reputable suppliers.
8. Cable types
- Flexible (fine-stranded) cable: for vehicles, boats and anywhere with vibration. Use crimp lugs made for fine strands. See the crimping guide.
- Tinned copper: resists corrosion in boats and damp places. See the boat wiring guide.
- Solar (PV) cable: double-insulated and UV resistant for outdoor panel runs.
- Welding cable: very flexible and often used for battery leads; check its voltage and temperature rating.
- Never use copper-clad aluminium for high-current DC.
9. Fusing the cable
- Fit a fuse or breaker as close as practical to the battery (or other source) on every positive cable.
- The fuse rating should be above the normal load current (commonly about 1.25 × the continuous current) and no higher than the cable's current rating.
- If you increase a fuse, you may need a bigger cable.
- See the fuse size calculator and the busbars and DC distribution guide.
10. Frequently asked questions
What size cable do I need for a 12 V 20 A load 5 metres away?
For a 3% drop: 2 × 5 × 20 × 0.0172 ÷ 0.36 = 9.6 mm², so 10 mm².
Why does my inverter cut out under load when the battery is full?
Often voltage drop in undersized or poorly crimped cables. Measure the voltage at the inverter terminals under load and compare it with the battery.
Is thicker cable ever a problem?
Only for cost, weight and fitting into terminals. Electrically, a bigger cable is never less safe, as long as the fuse still suits the smallest cable in the circuit.