Inverter cable size and fuse calculator

Inverters draw very high currents from the battery. Enter the inverter's continuous rating and the cable length to get the fuse and the cable that fuse protects.

W
V
12, 24 or 48. The calculator allows for the battery sagging to about 90% of nominal under heavy load.
%
Keep inverter cables as short as possible, ideally under 2 m.

Results

Battery current at full load—
Battery fuse—
Cable size—
Voltage drop at full load—
Cable limited by—

How it works

Battery current = Inverter watts ÷ efficiency ÷ (0.9 × battery voltage) Fuse ≥ 1.25 × battery current (next standard size) Cable: rated above the fuse, and thick enough for the voltage drop limit

The cable must be rated for at least the fuse size, because the fuse is there to protect the cable. Surge (motor-start) current is short enough that fuses ride through it; size for the continuous rating.

Quick chart: 105 °C cable, 1.5 m run, 2% drop

Inverter12 V current / fuse / cable24 V current / fuse / cable48 V current / fuse / cable
600 W62 A / 80 A / 16 mm²31 A / 40 A / 4 mm²15 A / 20 A / 1–1.5 mm²
1,000 W103 A / 150 A / 25 mm²51 A / 70 A / 10 mm²26 A / 35 A / 2.5 mm²
2,000 W206 A / 300 A / 70 mm²103 A / 150 A / 25 mm²51 A / 70 A / 10 mm²
3,000 W309 A / 400 A / 95 mm² (better at 24 V)154 A / 200 A / 35 mm²77 A / 100 A / 16 mm²
5,000 WNot practical257 A / 350 A / 95 mm²129 A / 175 A / 25 mm²

Rounded results from this calculator at 90% efficiency. Always follow the inverter maker's minimum cable and fuse sizes, which can be larger.

Good practice

For other circuits, use the DC cable size calculator and the fuse size calculator.

Current ratings are guide figures; check the cable maker's ratings and derate in hot locations.

Frequently asked questions

What size cable do I need for a 2000W inverter at 12V?

About 206 A flows at full load, so a 300 A fuse and around 70 mm² (2/0 AWG) 105 °C cable for a short run. At 24 V it's 25 mm² with a 150 A fuse.

What size fuse for a 3000W inverter?

At 12 V about 400 A; at 24 V about 200 A; at 48 V about 100 A. Higher voltages make big inverters far easier to wire.

Should I size inverter cable for the surge rating?

No. Size the fuse for the continuous current and the cable for the fuse. Surges last only seconds and fuses are designed to ride through them.