Lightning and surge protection for off-grid systems
How lightning damages equipment, when you need protection, earthing and bonding, types of surge protection device, and protecting solar arrays, wind turbines, radio antennas, vans and boats.
By Michael Johnson · Updated 17 November 2026 · How we check our guides
Off-grid homes, sheds and cabins are often the tallest thing around, with long cable runs to solar arrays, wind turbine masts and radio antennas. That makes them vulnerable to lightning: not usually a direct strike, but surges induced in long cables by strikes nearby, which can destroy charge controllers, inverters and radios. This guide covers how lightning damage happens, earthing and bonding, surge protection devices for solar, wind and antennas, and what the standards say.
1. How lightning damages equipment
- Direct strikes carry tens of thousands of amps. Only a properly designed lightning protection system (air terminals, down conductors and earth electrodes) handles them.
- Induced surges are far more common: a strike hundreds of metres away induces voltage spikes in long cables, especially solar, wind and antenna feeders.
- Earth potential rise: a strike nearby raises the ground voltage. If equipment is earthed at two different points, current flows between them through your electronics.
- The answer to the last two is bonding everything to one earth system and fitting surge protection at each point where a cable enters the building.
2. Do you need protection?
| Situation | Risk | Suggested protection |
|---|---|---|
| Van or caravan with roof panels | Low | None special; good fusing and wiring |
| Shed with a short run to roof panels | Low to moderate | Bond panel frames; SPD if the controller is expensive |
| Ground-mounted array with long cables | Moderate to high | DC SPDs at both ends, bonded frames, earth electrode |
| Wind turbine on a tall mast | High | Earthed mast, SPDs, mast earth bonded to the system earth |
| Radio antennas and towers | High | Coax lightning arrestors at the entry, single-point earth |
| Exposed hilltop site, high lightning area (much of the US and northern Australia) | High | A risk assessment and lightning protection system to BS EN 62305 / NFPA 780 / AS/NZS 1768 |
3. Earthing and bonding: the foundation
- Use one earthing system: bond the solar frames, mast, antenna earth, electrical installation earth and metal water pipes together, so everything rises and falls together.
- Keep earth conductors short and straight, with gentle bends: lightning current doesn't like sharp corners.
- Separate earth rods must be bonded together, not left as isolated "dedicated" earths.
- An earth rod at the base of a mast or array, bonded to the main earth, gives surge current a short route to ground.
- See the off-grid earthing guide.
4. Surge protection devices (SPDs)
| Type | Where | Protects against |
|---|---|---|
| Type 1 | Main incoming supply, where there's a lightning protection system or overhead lines | Partial direct lightning currents |
| Type 2 | Consumer unit, inverter AC output, PV DC input | Induced surges (the most common choice) |
| Type 3 | Close to sensitive equipment | Residual surges |
| Coax arrestor (gas discharge tube) | Antenna feeder entry | Surges on radio cables |
- DC SPDs must be rated for DC and for the system's maximum voltage (for solar, above the array's cold-weather open-circuit voltage).
- An SPD only works with a short, low-impedance connection to earth: keep its earth lead under about 0.5 m.
- SPDs wear out. Many have an indicator window; replace them after a big storm if the indicator shows.
- In the UK, BS 7671 requires a surge risk assessment for new installations, and SPDs are now fitted to most new consumer units.
5. Solar arrays
- Bond the panel frames and mounting rails to earth with a suitable conductor (often 6–16 mm² copper).
- Fit a DC SPD at the charge controller or inverter input, and another at the array if the cable run is over about 10 m.
- Run positive and negative cables together to reduce the loop area that picks up induced voltages.
- Put DC isolators where you can disconnect the array quickly.
- See the charge controller guide and the MPPT string voltage calculator for the maximum voltage.
6. Wind turbines and masts
- Earth the mast at its base with an earth rod, bonded to the main earth system.
- Fit an SPD on the turbine cable where it enters the building, and at the controller.
- Metal guy wires should be bonded to earth at their anchors.
- See the small wind turbine guide.
7. Radio antennas
- Fit a coax lightning arrestor at the point the feeder enters the building, bonded to an earth rod there, and bond that rod to the main electrical earth.
- Use a single entry panel for all cables (antenna, rotator, solar) so everything is earthed at one point.
- Disconnect antennas from the radio and earth them when storms are forecast. An arrestor reduces damage; disconnection prevents most of it.
- For antenna design, coax loss and band plans, see ShackWiki; for off-grid radio set-ups, see the emergency communications guide.
8. Vans and boats
- A metal-bodied vehicle protects the people inside (a Faraday cage effect); a strike can still damage electronics.
- On sailing boats, the mast is the obvious target. A bonded, low-resistance path from the masthead to a submerged ground plate is the main protection; ABYC E-4 covers lightning protection for boats.
- Disconnect shore power and antennas when a storm approaches if you can do it safely.
9. Frequently asked questions
Do I need lightning protection for my solar panels?
For roof panels with short cables on a van or house, usually just good bonding. For ground-mounted arrays with long cables, or in high-lightning areas, fit DC surge protection at both ends and bond the frames to earth.
What is a surge protection device?
A device that diverts the voltage spike from a nearby lightning strike to earth before it reaches your equipment. Type 2 SPDs are the usual choice for homes and solar systems.
Should I disconnect my antenna in a thunderstorm?
Yes, when storms are forecast. Disconnect the feeder from the radio and earth it. An arrestor reduces damage but disconnection is more reliable. Don't touch antennas once thunder is heard.
Does an earth rod protect against lightning?
On its own, not much. It helps when it's part of a bonded system with surge protection at every cable entry.
10. Sources
- ARRL, lightning protection: arrl.org
- ARRL, grounding and bonding for the amateur: arrl.org
- Electrical Installation Guide (Schneider Electric), SPD for photovoltaic applications: electrical-installation.org
- IAEI Magazine, surge protection for photovoltaic systems: iaeimagazine.org
New to some of the terms? See the glossary. Not sure where to start? Try start here.