The formula
This ignores cable reactance, which is small for cables under about 25 mm². For larger cables use the cable maker's mV/A/m figures.
Design limits
| Country | Rule or guidance |
|---|---|
| Australia | AS/NZS 4777.1 limits voltage rise from the inverter to the point of supply to 2% in total; designers often target about 1% in the inverter's own cable |
| UK | Grid voltage can legally rise to 253 V (230 V +10%); inverters trip on over-voltage under G98/G99 settings. Designers commonly keep inverter cable rise to around 1% |
| USA | The NEC's informational notes suggest 3% for branch circuits and 5% overall for voltage drop; many PV designers keep AC rise to 1–2% |
Why it matters
On sunny days with many solar homes on one street, grid voltage is already high. Each inverter must raise its output voltage to push power out, and if it reaches its trip limit it shuts down or throttles output, losing you generation. A larger AC cable is the usual fix.
For DC cables, see the DC voltage drop calculator; for AC loads, the AC voltage drop calculator.
Frequently asked questions
What is voltage rise in solar?
The extra voltage an inverter must produce to push its output through the cable to the grid. It equals the voltage drop in that cable at the inverter's output current.
What is the maximum voltage rise allowed in Australia?
AS/NZS 4777.1 limits the total voltage rise from the inverter to the point of supply to 2%.
How do I reduce voltage rise?
Use a larger cable, shorten the run, or (with the network's agreement) use the inverter's power-quality modes. Three-phase connection also helps.