Generators: choosing, sizing and running one safely
Everything about portable, inverter and standby generators: power ratings, sizing for motor start-up surges, power quality for electronics, where to put one, leads and RCDs, fuel storage, noise, emissions rules including California's, maintenance, and the regulations in the UK, USA and Australia.
By Michael Johnson · Updated 16 November 2026 · How we check our guides
1. Types of generator
| Type | Typical size | Good for | Watch out for |
|---|---|---|---|
| Inverter generator (petrol or dual-fuel) | 1–7 kW | Electronics, camping, vans, home backup of essentials. Quiet, fuel-efficient at light load, clean power | Costs more per kW; small units struggle with big motor starts |
| Open-frame (conventional) with AVR | 3–12 kW | Power tools, building sites, whole-house backup through a transfer switch at low cost | Loud (70–75 dB(A) at 7 m), thirsty at light load, rougher waveform on cheap models |
| Dual-fuel or tri-fuel | 2–12 kW | Running on LPG/propane (stores indefinitely) as well as petrol; tri-fuel adds natural gas | About 5–15% less output on gas |
| Diesel portable or towable | 5–30 kW | Long runtimes, farms, remote cabins, motorhomes | Heavy, noisy, expensive; "wet stacking" if run lightly loaded |
| Standby (fixed, automatic) | 8–26 kW home sizes | Whole-house backup with automatic start, on mains gas, LPG or diesel | Installation, permits and annual servicing |
| Cheap two-stroke "suitcase" | 0.6–1 kW | Very occasional light use | Poor waveform, noisy, oily fuel mix, short life; avoid for electronics |
If what you really need is quiet power for a few devices, a battery may be better. See the portable power station guide.
2. Power ratings explained
- Running (rated, continuous) watts: what the generator can supply for hours. Use this for sizing.
- Starting (peak, surge, maximum) watts: what it can supply for a few seconds to start motors. Brochures often print this in the largest type.
- kVA versus kW: kW = kVA × power factor. Larger generators are often rated in kVA at a power factor of 0.8, so a "10 kVA" set gives about 8 kW of real power.
- Standby, prime and continuous ratings (ISO 8528-1): standby (ESP) ratings assume emergency use only, with limited hours a year; prime (PRP) ratings allow unlimited hours at varying load; continuous (COP) ratings are for constant full load. A standby-rated set run as your daily power will be overworked.
- Altitude and heat: naturally aspirated engines lose power as air thins and warms, typically around 3–4% per 300 m (1,000 ft) above a few hundred metres, and more in hot weather. Follow the maker's derating table.
3. Sizing for motors and surges
- List everything that may run at once and add the running watts.
- Find the biggest motor and how much extra it needs to start (starting minus running). Fridges, freezers, pumps and air conditioners typically need 2–7 times their running power for a second or two.
- Your generator's running rating must exceed step 1, and its peak rating must exceed step 1 plus step 2.
- Aim to keep the steady load at 50–80% of the running rating.
- Start motors one at a time. Turn on the biggest motor first, then the others.
- Soft-starters fitted to air conditioners and pumps cut the start-up surge by roughly half to two-thirds, often letting a much smaller generator run them.
- Induction loads and power factor: motors draw more current than their watts suggest. A generator rated 3,000 W may only handle about 2,400–2,700 W of motor load.
- Use the generator size calculator to check your own list, and see the load table in the home backup power guide.
4. Power quality and electronics
- Waveform. Inverter generators make DC and then convert it to a clean sine wave, typically with total harmonic distortion (THD) under 3%, much like the mains. Cheaper conventional generators can reach 5–25% THD.
- Frequency. A conventional generator's frequency depends on engine speed and droops under load (for example from 52 Hz unloaded to 49 Hz at full load on a 50 Hz set). Inverter generators hold frequency steady.
- What cares. Battery chargers, inverter-chargers, variable-speed boiler and furnace boards, induction hobs, laptops and some medical devices can reject, misread or be damaged by rough power. Use an inverter generator, or a conventional set with good automatic voltage regulation (AVR) and a stated THD under 6%.
- Battery chargers on generators. Many inverter-chargers have a "generator" or "weak AC" setting that widens the accepted frequency range and limits charging current. Use it.
5. Where to put it
- Outdoors only, on firm, level, dry ground, with at least a metre of clear space around it for cooling.
- Point the exhaust away from buildings, tents and vehicles. In the US, CPSC advises at least 20 feet (6 m) from the house.
- In rain, use a canopy or enclosure designed for generators. Don't cover it with a tarp; it traps heat and fumes.
- Keep it clear of dry grass, fuel cans and anything combustible; the exhaust and muffler get hot enough to ignite them.
- Lock it to a fixed point; generators are a favourite target for thieves after storms.
6. Electrical safety: outlets, RCDs and leads
- Plug appliances in directly, or use heavy-duty outdoor extension leads. To power house circuits, an electrician must fit an inlet and changeover or transfer switch. See the home backup power guide; never use a double-ended lead.
- RCD and GFCI protection. Protect every outdoor lead with a 30 mA RCD (UK, Australia) or a GFCI (US). Some generators have it built in. On a generator with a floating neutral, a plug-in RCD may not trip on an earth fault; check the generator manual.
- Earthing. Most small portable generators supplying equipment plugged into their own outlets don't need an earth spike (US NEC 250.34 says so explicitly). Larger sets, sets feeding fixed wiring, and some site uses do; follow the manufacturer and your electrician.
- Building sites (UK). Site tools run at 110 V from a centre-tapped-earth transformer or 110 V generator (BS 7375 and BS 7671 Section 704). Australian construction sites need RCD-protected outlets (AS/NZS 3012).
- Uncoil cable reels fully. A coiled reel can overheat at currents well below its rating.
Extension lead voltage drop
| Lead | Current | 1.5 mm² / 14 AWG | 2.5 mm² / 12 AWG | 4 mm² / 10 AWG |
|---|---|---|---|---|
| 230 V, 25 m | 10 A | 5.8 V (2.5%) | 3.5 V (1.5%) | 2.2 V (1.0%) |
| 230 V, 50 m | 10 A | 11.7 V (5.1%) | 7.0 V (3.0%) | 4.4 V (1.9%) |
| 120 V, 50 ft (15 m) | 15 A | 3.9 V (3.2%) | 2.4 V (2.0%) | 1.5 V (1.3%) |
| 120 V, 100 ft (30 m) | 15 A | 7.7 V (6.4%) | 4.8 V (4.0%) | 3.0 V (2.5%) |
Copper, out and back. Keep drop under about 5%, and under 3% for motors. Check other lengths with the AC voltage drop calculator.
7. Fuel choices and storage
| Fuel | Storage life | Pros | Cons |
|---|---|---|---|
| Petrol (gasoline) | 3–6 months; longer with stabiliser; 2+ years for alkylate fuel | Available everywhere, light generators | Ethanol blends (E10) absorb water and gum carburettors; highly flammable |
| LPG / propane | Indefinite in a sound cylinder | Clean burning, no stale fuel, easy starting after storage | 5–15% less power; cylinders need safe outdoor storage; see the LPG and propane safety guide |
| Natural gas (piped) | Unlimited supply while the gas network runs | No refuelling; ideal for standby sets | Network may also fail in earthquakes and floods |
| Diesel | 6–12 months; longer with treatment and dry tanks | Efficient, safer to store (high flash point), long engine life | Diesel bug and wax in cold; heavy, expensive sets |
- Estimate how much fuel you need with the generator fuel consumption calculator.
- UK: up to 30 litres of petrol at a home without notifying the petroleum enforcement authority, in suitable containers (plastic up to 10 L, metal up to 20 L). Keep it in a shed or garage away from the house's living space and ignition sources.
- US: local fire codes usually cap stored gasoline in and around a home (commonly 25 US gallons in approved cans). Use cans meeting ASTM F852 or UL 30 with child-resistant spouts. Don't store fuel in the basement.
- Australia: use containers marked AS/NZS 2906, and keep within your state's dangerous-goods limits for homes (check your state regulator before stockpiling).
- Refuel only with the engine stopped and cool. Never refuel in the dark with a naked flame or a phone screen as the only light.
8. Noise
| Source | Typical level |
|---|---|
| 2 kW inverter generator, eco mode | 50–58 dB(A) at 7 m |
| 3.5 kW inverter generator | 57–65 dB(A) at 7 m |
| Open-frame 5–8 kW | 70–76 dB(A) at 7 m |
| Enclosed home standby, 20 kW | 60–68 dB(A) at 7 m in exercise and full load |
- Every 10 dB(A) sounds roughly twice as loud. Doubling the distance cuts the level by about 6 dB(A) in the open.
- UK: generators sold for outdoor use must carry a guaranteed sound power label under the Noise Emission in the Environment by Equipment for use Outdoors Regulations 2001. Councils can act against noise nuisance under the Environmental Protection Act 1990.
- US: noise is mostly governed by city and county ordinances; many limit night-time levels at the property line and some exempt generators only during declared emergencies or utility outages. In national parks, 36 CFR 2.12 limits generator noise to 60 dB(A) at 50 feet, and many campgrounds set generator hours.
- Australia: state environment protection laws and council rules restrict noisy equipment at night and in residential areas; national parks often ban generators in some campgrounds or set hours.
9. Emissions and clean-air rules
- US federal: the EPA's Phase 3 standards cover small spark-ignition engines under 19 kW, including portable generators.
- California: CARB's small off-road engine (SORE) rules tightened limits for generator engines from model year 2024 and require new portable generator engines to be zero-emission from the 2028 certification model year, though a credit scheme could push the deadline back. Generators already bought can still be used. Several states follow some CARB rules; check before buying.
- UK: the retained EU non-road mobile machinery rules (Regulation 2016/1628, "Stage V") set emission limits for engines in new generators. Generators running near homes can also count as statutory nuisance if fumes or smoke affect neighbours.
- Australia: the Product Emissions Standards Act 2017 sets emission limits for new small petrol engines under 19 kW, including generators, based on US EPA standards, and phased in from July 2018. Equipment certified to US EPA, EU, Canadian or Californian standards is accepted.
- Smoke control areas (UK) and wood-heater rules apply to solid fuel, not generators. See the wood burner guide for clean-burning zones.
10. Maintenance schedule
| When | Task |
|---|---|
| Before each use | Check oil level, fuel, air filter, leads; clear debris from cooling vents |
| First 5–20 hours (new engine) | First oil change (running-in period; see manual) |
| Every 50–100 hours or yearly | Oil change, clean or replace air filter, check spark plug |
| Every 100–300 hours | Replace spark plug, clean spark arrester, check valve clearance (some engines) |
| Monthly | Run under load for 20–30 minutes; exercise standby sets automatically |
| Before storage | Run the carburettor dry or add stabiliser; change the oil; store dry with the fuel tap off |
| Diesel sets | Avoid long running below about 30–40% load (wet stacking); run at heavy load regularly; drain water from fuel filters |
11. Running two generators in parallel
- Many inverter generators can be linked with a parallel kit from the same maker, doubling output while keeping two light, portable units.
- Only parallel generators designed for it, with the correct kit. Never join two generators' outputs with home-made leads.
- Paralleled output is still a separate source: connect to a house only through an inlet and transfer switch.
12. Generators at campsites and in vans
- Many UK campsites restrict or ban generators, and those that allow them often set hours. Club rules vary; ask when booking.
- US national parks and many state parks set generator hours and the 60 dB(A) at 50 feet limit.
- Australian national parks often ban generators in some campgrounds; check each park's rules.
- For a van, a solar and battery system is usually better. See the campervan wiring guide. If you carry a generator, store petrol in a sealed, vented locker outside the living space, and never run it under an awning.
- Charging a leisure battery from a generator: plug the van's hook-up into the generator through a suitable lead, and use the charger's generator setting.
13. Rules by country
| UK | USA | Australia | |
|---|---|---|---|
| Connecting to house wiring | BS 7671 Section 551.6: changeover switch fitted by a competent electrician; Part P notification in England and Wales | NEC Article 702: listed transfer switch or interlock, under a permit | AS/NZS 3000 Section 7.3 and AS/NZS 3010: licensed electrician, changeover switch, certificate of compliance |
| Generator product standards | UKCA/CE marking; BS EN ISO 8528-13 for portable set safety | UL 2201 (portable generator safety, including CO), PGMA G300 (safety and performance); NEC 445 | AS/NZS 3010; RCM marking; AS/NZS 3012 for construction sites |
| Carbon monoxide | CO alarms to BS EN 50291; landlord CO alarm rules in England, Scotland and Wales | CPSC: 20 ft from home, CO shut-off models; state CO alarm laws | State safety regulators: outdoors only, away from openings |
| Emissions | Stage V NRMM limits | EPA Phase 3; CARB SORE (zero-emission from 2028 model year) | Product Emissions Standards Act 2017 |
| Noise | Outdoor equipment noise labels; council nuisance powers | Local ordinances; 36 CFR 2.12 in national parks | State EPA noise rules; council and park rules |
| Fuel storage at home | 30 L petrol without notification | Local fire code, often 25 gal gasoline | State dangerous-goods limits; AS/NZS 2906 containers |
14. Buying checklist
- Running watts at least 25% above your steady load, and peak watts covering your biggest motor start.
- Inverter type if you'll run electronics, chargers or a boiler, or need quiet running.
- The right outlets: 240 V twist-lock (US L14-30) or 16/32 A blue industrial socket (UK, Australia) if you plan an inlet and transfer switch.
- CO shut-off (US: UL 2201 or PGMA G300 certified).
- Electric start and a low-oil shut-off.
- Fuel type you can store safely; consider dual-fuel.
- Noise rating at 7 m, and eco or idle mode.
- Local dealer support and parts availability.
- Correct regional approval marks: UKCA/CE, UL/ETL, RCM.
15. Frequently asked questions
Is an inverter generator worth the extra cost?
For electronics, battery charging, boilers, camping and anywhere noise matters, yes. Inverter generators are quieter, use less fuel at light load and give clean power. For power tools or whole-house backup on a budget, a good open-frame generator with AVR is fine.
Can I run a generator in my garage with the door open?
No. Carbon monoxide builds up in garages and seeps into homes even with the door open. Run it outside, at least 20 feet (6 m) from the house in US guidance, with the exhaust pointing away.
Do I need to earth (ground) my portable generator?
Usually not when you only plug appliances into its own outlets; US NEC 250.34 says so explicitly, and most makers agree. When a generator feeds house wiring, an electrician will set up the earthing as part of the transfer switch installation.
How long can a generator run continuously?
Portable petrol generators run until the tank is empty, typically 4–12 hours, and can be refuelled after cooling down. Check the oil every 8–24 hours of running. Standby sets on mains gas can run for days, with oil checks as the maker specifies.
Will California's rules stop me using my petrol generator?
No. CARB's rules apply to new generator engines sold in California from the 2028 certification model year (possibly later with credits). Existing generators can still be used.
Why does my battery charger reject generator power?
Probably because the generator's frequency or waveform is outside the charger's limits. Use the charger's generator or weak-AC mode, reduce the charge current, or use an inverter generator.
16. Sources
- US CPSC, portable generator CO safety and certified standards (2025): cpsc.gov
- EC&M, NEC requirements for generators: ecmweb.com
- RVIA, CARB regulation on small off-road engines explained: rvia.org
- CARB, 2021 amendments to the small off-road engine regulations: arb.ca.gov
- Australian Government, Product Emissions Standards Act 2017: legislation.gov.au
- Electrical Safety Office Queensland, portable generators (AS/NZS 3010): electricalsafety.qld.gov.au
- Energy Safe Victoria, generator safety fact sheet (2026): energysafe.vic.gov.au
- Government of South Australia, using generators for back-up power: sa.gov.au
- US National Park Service regulations, 36 CFR 2.12 audio disturbances: ecfr.gov
- UK legislation, Noise Emission in the Environment by Equipment for use Outdoors Regulations 2001: legislation.gov.uk
- UK legislation, Petroleum (Consolidation) Regulations 2014: legislation.gov.uk
General guidance only. Follow your generator manufacturer's instructions, and use a qualified electrician for any connection to fixed wiring.